    1. Product overview and application scope
      KYN28-12 metal-enclosed switchgear (hereinafter referred to as switchgear) is a new type of product designed and developed by the company on the basis of absorbing advanced manufacturing technology at home and abroad, which can replace a variety of old type metal-enclosed switchgear, such as KYN1-10, JYN2-10, GBC-10 and other products. Its products have the following obvious advantages:
      1.1 The shell of the product is completely assembled by bolts after multiple bending and forming of the aluminum-clad steel plate processed by CNC machine tool, which has high mechanical strength and effectively ensures the neat and beautiful appearance of the product. The cabinet door is sprayed with plastic coating, which has strong impact resistance and corrosion resistance. The product housing has IP4X level of protection.
      1.2 The main switch of this product can be configured with VY4, VD4 series vacuum circuit breaker, C3 series fixed load switch, and can also be configured with a variety of domestic series vacuum circuit breaker (such as VS1, VH1, VK, ZN28) to replace similar foreign products.
      1.3 No matter what type of circuit breaker is selected, the bare conductor air insulation distance must be greater than 125mm, and the composite insulation must be greater than 60mm. The circuit breakers have the unique advantages of long life, high parameters, less maintenance and small size.
      KYN28-12 armoury medium metal enclosed switchgear is suitable for 3.6-12KV three-phase AC 50Hz power grid to receive and distribute electrical energy, and to control, monitor and protect the circuit. Can be used in single bus, single bus segment system or double bus system. Switchgear conforms to IEC298 “Rated voltage above 1KV 52KV and below AC metal enclosed switchgear and control equipment”, IEC694 “High voltage switchgear and control equipment Regulations”, China GB3906 “3-35KV AC metal enclosed switchgear” and DL404 “Indoor AC high voltage switchgear ordering conditions”, German DIN.VDE670 “AC switchgear with rated voltage above 1KV” and other standards. And it has perfect and reliable anti-misoperation function.
    2. Model meaning
    1. Normal operating conditions
      3.1 Ambient air temperature: upper limit +40℃, lower limit -10℃;
      3.2 Relative humidity: the daily average is not more than 95%; The monthly average is not more than 90%;
      3.3 Altitude: no more than 1000m;
      3.4 Earthquake intensity does not exceed 8 degrees;
      3.5 No fire, explosion danger, serious pollution, chemical corrosion and violent vibration occasions, when the use of conditions beyond the above scope, should be negotiated by the user and our company to determine the scope and technical measures.
    2. Technical parameters
      4.1 Technical Specifications of the switchgear
    entrySingle positionparameter
    Rated voltagekV3.6、7.2、12
    Rated frequencyHz50
    Circuit breaker rated currentA630、1250、1600、2000、2500、3150
    Rated current of switchgearA630、1250、1600、2000、2500、3150
    Rated dynamic stability current (4s)kA16、20、25、31.5、40、50
    Rated dynamic stable current (peak)kA40、50、63、8、100、125
    Rated short-circuit breaking currentkA16、20、25、31.5、40、50
    Rated short-circuit switch closing current (peak)kA40、50、63、80、100、125
    Rated insulation level1m?in power frequency withstand voltagekV243242
    Lightning impulse, withstand voltagekV406075
    Class of protectionThe enclosure is IP4X, and the compartment and circuit breaker room doors are IP2X when opened
    Basic form of the dimensions of the switchgear (see Figure 1, Figure 2)
    5.1 The construction of the installation foundation of the switch cabinet shall comply with the relevant provisions of the “Technical Specification for Electric Power Construction and Acceptance”.
    5.2 The installation foundation of the switch cabinet is generally divided into two pours of concrete. The first installation of components for the switch cabinet is the installation foundation of Angle steel or square steel and channel steel components. The second pouring concrete is the supplementary layer of the ground, the general thickness is 60mm, and the concrete height should be 1-3mm lower than the component plane when pouring the supplementary layer of concrete.

    A busbar compartment
    B circuit breaker compartment
    C cable compartment
    D instrument compartment
    Shell
    1.1 pressure release plate
    1.2 control cable cover
    2. branch busbar
    3. busbar
    4. static contact device
    5. spring contact
    6. grounding knife
    7. current transformer

    8. voltage transformer
    9. removable partition
    10. secondary plug
    11. auxiliary switch
    12. movable curtain plate
    13. removable trolley
    14. grounding knife operating mechanism
    15. cable sealing terminal
    16. bottom plate
    17. screw mechanism
    18. grounding main busbar
    19. removable horizontal partition

    KYN28-12 switch cabinet basic structure diagram

    Figure 1 Dimensions of the switchgear

    Figure 2 Basic form

    發(fā)表回復(fù)

    您的郵箱地址不會被公開。 必填項(xiàng)已用 * 標(biāo)注

    国产伦精品免编号公布| 久久国产精品2020盗摄| 九九精品成人免费国产片| 91精品观看91久久久久久| 久9视频这里只有精品8| 国产亚洲精品资在线| 国产精品影音先锋| 亚洲精品无码日韩国产不卡?V| 久久精品噜噜噜成人av| 日韩AV无码精品一二三区| 久久精品国产亚洲网站| 精品久久久无码人妻中文字幕豆芽| 精品少妇一区二区三区在线| 久久香蕉国产线看精品| 精品久久久久久99人妻| 国产精品成人网站| 99久久人妻精品免费一区| 八戒久久精品一区二区三区| 亚洲蜜芽在线精品一区| 国产情侣大量精品视频| 国产成人亚洲精品播放器下载 | 2020国产精品视频| 国内揄拍高清国内精品对白| 国产精品伊人久久伊人电影| 2021国产精品久久精品| 国产精品污WWW在线观看| 久久久久人妻一区精品果冻| 狠狠色香婷婷久久亚洲精品| 91精品啪在线观看国产91九色 | 国产成人亚洲精品| 久久精品无码午夜福利理论片| 九九久久国产精品免费热6| 91精品91久久久久久| 老汉精品免费AV在线播放| 亚洲国产精品久久久久婷婷软件| sss视频在线精品| aaa级精品久久久国产片| 亚洲性日韩精品国产一区二区| 伊人久久精品影院| 精品97国产免费人成视频| 精品久久久无码中文字幕|